Product Description
. . . . . Simplex Grinnell 4090-9007 743-357 IDNet Signal IAM Individual Addressable Module
Signal IAMs provide additional selective signaling for Simplex® 4007ES, 4008, 4010ES, 4100ES, and 4100U Series fire alarm control panels: Signal output notification appliance circuit (NAC) wiring is supervised and connected to the signal input under IDNet communications control NAC output is rated 0.5 A for Special Application or Regulated 24 VDC Appliances, or for audio operation (12.5 W @ 25 VRMS, 35 W @ 70.7 VRMS); and can be wired Class B or Class A; see additional information on page 2, specifications section Signal coding of horn/strobe control, strobe synchronization, or other coding is provided by the signal input; coding at the Signal IAM via IDNet addressable communications is not supported 4100U compatibility requires Software Revision 11.11.01 or higher Signal IAMs are not compatible with 4010 fire alarm control panels IDNet communications.. Simplex Grinnell. TE Connectivity. 4090-9007.