Product Description
Duct Sensor Housing with Supervised Multiple Relay Output. Requires Separate 24 VDC Fire Alarm Power and 4081-9008 End-of-Line Resistor Harness. Includes One 4098-9843 Relay. Compatible With: Simplex fire alarm control panel models: 4100ES, 4010ES, 4008, 4010, 4100U, and legacy products 4020, 4100/4100+, and 4120.. . TrueAlarm Analog Sensing Addressable Duct Sensor - Duct sensor housing with supervised output for multiple remote relays; requires separate 24 VDC; includes one relay ï'· Relay output is under panel control. At the panel, relay output can be activated manually or in response to a separate alarm or other input. Includes factory installed TrueAlarm photoelectric smoke sensor and features: Individual sensor information processed by the host control panel to determine sensor status. Digital transmission of analog sensor values via IDNet or MAPNET II, 2-wire communications. Programmable sensitivity, consistent accuracy, environmental compensation, status testing, and monitoring of sensor dirt accumulation. UL listed to Standard 268A. Clear cover allows visual inspection. Test ports provide functional smoke testing access with cover in place. Mounts to rectangular ducts or round ducts; minimum size is 8†(203 mm) square or 18†(457 mm) diameter. Magnetic test feature for alarm initiation at housing. Optional weatherproof enclosure is available separately (refer to data sheet S4098-0032). Diagnostic LEDs (on interface board): Red Alarm/Trouble LED for sensor status and communications polling display. Yellow LED for open or shorted trouble indication of supervised relay control (4098-9756 only).. Simplex Grinnell. TE Connectivity. 4098-9756.